Thermal Event at Datacenter

02-07-10 by . 18 comments

Our hosting provider, PEAK, let us know that they had a cooling compressor fail in the facility.

The primary database server was apparently taken offline at 2:53 AM Pacific Time by this thermal event.

The backup database server is still online and has the most recent (12 AM) backups restored to it; we’re currently just waiting to hear if db1 is rebootable/alive before bringing db2 online.

db1 came back OK, and we’re resuming site service now at 3:57 AM.

Checking the logs, db1 apparently shut down from heat at 2:44 AM:

The previous system shutdown at 2:44:21 AM on 2/7/2010 was unexpected.

I suspect db1 shut down because it’s on top of the rack (highest = more heat) and it is the only server using the High Performance power plan — which operates all CPUs at 100% speed all the time — instead of the default Balanced power plan which allows the CPUs to reduce speed and consume less power when they are lightly loaded.

We’ll be following up with PEAK to figure out why this wasn’t handled before temperatures became dangerously high.

Obligatory video link.

Geoff went down to the datacenter, and he confirmed it really was quite hot down there — doors were open, fans were placed blowing air in, etc.

Update: PEAK official statement

The PEAK HVAC system consist of two cooling systems which both operate to provide cooling to the pressurized floor of data center. One system is a 5-ton and the second is a 10-ton unit.

At around 2:30am on Sunday morning (2/7) the PEAK Data Center experienced a failure of one of our air conditioning units on the roof. Our monitoring systems notified the PEAK support center when the AIR temperature exceeded 80 degrees F. At some point we measured temps of 83+ degrees F in the Data Center.

Engineers arrived on-site around 3:00am and deployed portable fans to exhaust warm air. This brought down the air temperature in the Data Center to under 80 degrees.

Our HVAC vendor was dispatched and arrived on-site by 4:00am. The vendor located a failed heat exchanger fan motor in their in-stock inventory and performed an emergency replacement. By 7:00am the HVAC system was operating with the repaired equipment. At 7:30 4lbs of coolant was added to the system. By 9:00am, the temperature in the Data Center returned to normal levels.

PEAK Engineers are looking into why this failure caused a significant rise in the Data Center temperature. Based on our findings, PEAK will take the necessary actions to ensure a failure of one systems does not cause a significant change in the Data Center temperature. We will provide this information once it becomes available.

Scary how fast temperatures rose!

Filed under server

18 Comments

Sam152 Feb 7 2010

Damn, this is the second time Peak has pretty much screwed us over.

Markus Feb 7 2010

*crossing fingers*

Wish/Dream: have a static HTML dump as a replacement available in case of DB outages so at least the existing Q/A can be browsed (can Google/YourBelovedSearchEngine be used for that?).

Wow, this really sucks; I guess I didn’t realize my addiction to this site until it was offline.

Doekman Feb 7 2010

An event you were bound to miss ;-)

Glad everything is up and running again…

I believe you should have a frequent offsite backup plan if PEAK blows up all servers.

we copy 10+GB data to Fog Creek’s NYC data center every weekend. The copy takes over 24 hours currently.

This is why you need redundant climate control systems.

http://www.pair.com/about/data_center_tour/tour2.html

Wow. You guys sure are taking your licks! Fortunately it was mostly a “drill” since you didn’t lose any hardware and hopefully not very much data.

It’s unclear to me if you failed over to your db2 server or if you waited it out to see if db1 would be back up in time. If you waited for db1, then I guess you had *no* data loss?

Thanks for sharing candidly the goings on behind the scenes!

your ability to find “relevant” videos is… scary.

Wow! They have a single cooling system for their datacenter? That’s completely unacceptable for a “professional” operation. Now if you’re redundant system has trouble keeping up on a hot August mid-day, I can appreciate the bean-counters constrained your environment. I’d compare single cooling failures to running without any sort of backup power, or running a server without ever taking backups. (For the cynical, I’m SA of a small environment where my uptime is 5 digits. Failure is a fact of life, get redundancy).

Looking forward to hearing the outcome of this.

Amusingly, the captcha below wants me to type “over melton” ;)

Matt Rogish Feb 8 2010

Yeah, you might want to look at a N+1 redundant data center. Totally unacceptable for this to happen.

@Matt
>Totally unacceptable for this to happen.
You might want to check your SLA with a free web site

As somebody smarter said on the podcast, the trick is scaling form one db to the second one – I suspect the really tricky bit is scaling from one data center to a pair of geographically remote ones.

I’m surprised no one has posted this link yet:

http://thedailywtf.com/Articles/Classic-WTF-Keepin-It-Cool.aspx

At least your hardware survived.
I left my laptop on the couch, must have been blocking the air inlets – came back to a dead laptop.

Looks like the CPU died.

Geoff said the servers were uncomfortable to touch when he was down there — as in, he could not leave his hand on the frame of the server for more than a few seconds.

Scary stuff!

How is the db2 sql server setup? You mentioned having the 12 am backup restored to it, so I’m assuming your not using database mirroring or replication? I’m curious because I would like to set a backup sql server for one of my sites and didn’t know if you experienced any issues getting that going for a site with such large volume.

George Duntley Feb 10 2010

Thank you I can use this as an example on why to monitor for my project. Still I am glad nothing major got broken forever.